EMI Filters and RFI Filters - Facility/Shielded Room Power Line Filters 
The F series EMI & RFI filters are designed to meet or exceed the requirements of MIL-STD-220
with 100 dB attenuation from 14 KHz or 100 KHz to 10 GHz.
General Specifications
- Attenuation (insertion loss) is 100 dB @ 14 KHz or 100 KHz to 10 GHz measured in
accordance with MIL-STD-220. Filter insertion loss will extend to 40 GHz when
installed with oroper EMI shielding and isolation.
- Filter cabinets are supplied with separate removable covers to access input
and output terminals. The output compartment is supplied with an EMI (RF)
non-corrosive, environmental gasket to prevent RF leakage and accommodate
maximum isolation between input and output compartments. The input compartment
is supplied with a moisture resistant gasket.
- Filters comply with applicable requirements of MIL-PRF-15733, MIL-STD-810
and UL 1283.
- Bleeder resistors are built into each filter line to discharge the capacitor
voltage to ground during power shutdown.
- Designed to operate continously at rated currents and voltages and are
capable of withstanding a 40% current overload for 15 minutes without
degradation.
- Voltage drop across each filter line at room temperature and full rated
current is less than 1%.
- Electrical Specifications: 120/208 or 277/480 VAC, 50/50 Hz.
EMI filters and RFI filters made in the USA
FACILITY/SHIELDED ROOM POWER LINE EMI & RFI FILTERS PRODUCT LINE
|
 |
|
 |
F Series Multi Line EMI Filters, 100 dB @ 14KHz
Data Sheet (PDF) |
 |
 |
F Series Multi Line EMI Filters, 100 dB @ 100KHz
Data Sheet (PDF) |
|
 |
F Series Single and Dual Line EMI Filters, 100 dB @ 14KHz
Data Sheet (PDF) |
|
|
|
|