LCR Electronics
Loading

EMI Filters and RFI Filters - Facility/Shielded Room Power Line Filters 

The F series EMI & RFI filters are designed to meet or exceed the requirements of MIL-STD-220 with 100 dB attenuation from 14 KHz or 100 KHz to 10 GHz.


                                        General Specifications

 

  • Attenuation (insertion loss) is 100 dB @ 14 KHz or 100 KHz to 10 GHz measured in accordance with MIL-STD-220.  Filter insertion loss will extend to 40 GHz when installed with oroper EMI shielding and isolation.
  • Filter cabinets are supplied with separate removable covers to access input and output terminals.  The output compartment is supplied with an EMI (RF) non-corrosive, environmental gasket to prevent RF leakage and accommodate maximum isolation between input and output compartments. The input compartment is supplied with a moisture resistant gasket.
  • Filters comply with applicable requirements of MIL-PRF-15733, MIL-STD-810 and UL 1283.
  • Bleeder resistors are built into each filter line to discharge the capacitor voltage to ground during power shutdown.
  • Designed to operate continously at rated currents and voltages and are capable of withstanding a 40% current overload for 15 minutes without degradation.
  • Voltage drop across each filter line at room temperature and full rated current is less than 1%.
  • Electrical Specifications: 120/208 or 277/480 VAC, 50/50 Hz.

 

EMI filters and RFI filters made in the USA

 

FACILITY/SHIELDED ROOM POWER LINE EMI & RFI FILTERS PRODUCT LINE

059-small_0.jpg
 	
F Series Multi Line EMI Filters

F Series Multi Line EMI Filters, 100 dB @ 14KHz    

Data Sheet (PDF)
059-small_0.jpg
 	
F Series Multi Line EMI Filters

F Series Multi Line EMI Filters, 100 dB @ 100KHz    

Data Sheet (PDF)
 
 	
F Series Single and Dual Line EMI Filters

F Series Single and Dual Line EMI Filters, 100 dB @ 14KHz    

Data Sheet (PDF)
 
 
 
059-small_0.jpg
EMI Filters Catalog (opens in new window)